BTL and Modbus are available only on GTM108 and GTC108.
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International. The BTL logo is a registered trademark of BACnet International.
The GTx108e-F/SI and GTx108e-F/DI are EBTRON’s solution for accurate and repeatable airflow measurement in SWSI (single inlet/outlet) and DWDI (double inlet/single outlet) fans. Airflow, temperature and/or airflow alarming are available on all models. Does not affect fan performance. Bluetooth® low energy technology interface.*
*Order with the /NR option when RF devices are not permitted.
Probe and Sensor Node Configurations
SWSI and DWDI fans: 2 probes x 1 sensor node/per probe in each fan inlet
Installed Airflow Accuracy¹
±(3% to 10%) of reading, depending on fan type and installation. May be improved by field adjustment using the Field Adjust Wizard (FAW) to a reliable reference.
Sensor Node Averaging Method
Airflow: Independent, arithmetic average
Temperature: Independent, velocity weighted average
Listings and Compliance
UL: UL-873 and CSA C22.2 No. 24
CE: European shipments only (EB-Link not available)
UKCA: UK shipments only
BACnet International: BTL Listed (GTC108 and GTM108 transmitters)
FCC:This device complies with Part 15 of the FCC rules
RoHS:This device is RoHS2 compliant
Environmental Limits
Temperature:
Probes: -20 to 160 ⁰F [-28.9 to 71.1 ⁰C]Transmitter: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]Humidity: (non-condensing)
Probes: 0 to 100%
Transmitter: 5 to 95%
Sensing Node Sensors
Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor
Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor
Sensing Node Housing
Material: Glass-filled Polypropylene
Sensor Potting Materials: Waterproof marine epoxy
Airflow Measurement
Accuracy: ±2% of reading to NIST-traceable airflow standards (includes transmitter uncertainty)
Calibrated Range: 0 to 10,000 fpm [0 to 50.8 m/s]Calibration Points: 16
Temperature Measurement
Accuracy: ±0.15 ⁰F [0.08 ⁰C] to NIST-traceable temperature standards (includes transmitter uncertainty)
Calibrated Range: -20 to 160 ⁰F [-28.9 to 71.1 ⁰C]Calibration Points: 3
Mounting Rods
Material: Zinc plated steel
Mounting Brackets
Material: 304 stainless steel
Mounting Options & Size Limits
Throat: 6 to 66 inches [152.4 to 1676.4 mm] (throat diameter)
Forward: 6 to 64 inches [152.4 to 1625.6 mm] (diameter at inlet entrance)
Face: 11 to 77 inches [279.4 to 1955.8 mm] (diameter at inlet entrance)
Probe to Transmitter Cables
Type: FEP jacket, plenum rated CMP/CL2P, UL/cUL listed, -67 to 302 ⁰F [-55 to 150 ⁰C], UV tolerant
Standard Lengths: 10, 25, and 50 ft. [3.1, 7.6 and 15.2 m]Connecting Plug: 9/16” [14.29 mm] nominal diameter with goldplated connector pins
Power Requirement
4 VAC (22.8 to 26.4 under load) @16V-A
Connector Receptacle Pins and PCB Connections: Gold-plated receptacle pins, PCB interconnects, PCB edge fingers, and test points
User Interface: 16-character LCD display and 4 button interface
B.A.S. Connectivity Options
All Transmitter: : Three field selectable (0-5/0-10 VDC or 4-20mA), scalable and isolated analog output signals (AO1=airflow,
AO2=temperature or alarm, AO3=Not used.
GTA108e Transmitter: : No additional connectivity to B.A.S
GTC108e Transmitter: : One additional field selectable (BACnet MS/TP or Modbus RTU) and isolated RS-485 network connection -Individual sensor node airflow rates and temperatures are available via the network
GTM108e Transmitter: One additional isolated Ethernet (simultaneously supported BACnet Ethernet or BACnet IP, Modbus
TCP and TCP/IP) network connection – Individual sensor node airflow rates and temperatures are available via the network
GTF108e Transmitter: One additional isolated Lonworks Free Topology network connection
GTU108e Transmitter: One additional USB connection for thumb drive data-logging of sensor node airflow rates and temperatures
Airflow Alarm
Type: Low and/or high user defined setpoint alarm
Tolerance: User defined % of setpoint
Delay: User defined
Zero Disable: Alarm can be disabled when the airflow rate falls below the low limit cutoff value (unoccupied periods)
Reset Method: Manual or automatic
Visual Indication: Yes, LCD display
Network Indication: Yes (GTM108 and GTC108 only)
Analog Signal Indication: Yes, on AO2 assignment
System Status Alarm
Type: Sensor diagnostic system trouble indication
Visual Indication: Yes, LCD display
Network Indication: Yes
Analog Signal Indication: Yes, on AO2 assignment
EB-Link Bluetooth Interface for Android® and iPhone®
Download individual sensor node airflow/temperature data, settings and diagnostics