Probe and Sensor Node Configurations
1 probe x 1 sensor node
2 probes x 1 sensor node/probe
Installed Airflow Accuracy¹
≤ 8 sq.ft. [0.74 sq.m.]:±(3% to 15%), typical (increases with increasing opening size). May be improved by field adjustment using the Field Adjust Wizard (FAW) to a reliable reference.
> 8 sq.ft. [0.74 sq.m.]: Not recommended.
Sensor Node Averaging Method
Airflow: Independent (arithmetic average on 2 sensor configurations installed at a single measurement location)
Temperature: Independent (velocity weighted or arithmetic average on 2 sensor configurations installed at a single measurement location)
Listings and Compliance
UL: 60730-1, 60730-2-9; CAN E60730-1, E60730-2-9 (EF-A2000-U Only)
FCC: This device complies with Part 15 of the FCC rules
RoHS: This device id RoHS2 compliant
Environmental Limits
Temperature:
Probes: 0 to 2,000 fpm [0 to 10.16 m/s]: -20 to 160 ⁰F [-28.9 to 71.1 ⁰F]
Probes: 0 to 3,000 fpm [0 to 15.24 m/s]: 0 to 160 ⁰F [-17.8 to 71.1 ⁰C]
Transmitter: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]
Humidity: (non-condensing)
Probes: 0 to 100%
Transmitter: 5 to 95%
Sensing Node Sensors
Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe
Temperature sensor: High-performance encapsulated chip thermistor with parylene coating
Sensing Node Housing
Material: Glass-filled Polypropylene
Sensor Potting Materials: Waterproof marine epoxy
Sensing Node Internal Wiring
Type: Kynar® coated copper
Airflow Measurement
Accuracy: ±3% of reading (typical), 4% max. to NIST-traceable airflow standards (includes transmitter uncertainty)
Calibrated Range: 0 to 3,000 fpm [0 to 15.24 m/s]Calibration Points: 7
Temperature Measurement
Accuracy: ±0.15 ⁰F [0.08 ⁰C] to NIST-traceable temperature standards (includes transmitter uncertainty)
Tube
Material: Mill finish 6063 aluminum
Mounting Brackets
Material: 304 stainless steel
Mounting Options & Overall Probe Length
Insertion: 6, 8 or 16 in. [152.4, 203.2 or 406.4 mm] (adjustable)
Stand-off: 6, 8 or 16 in. [152.4, 203.2 or 406.4 mm] (adjustable)
Probe to Transmitter Cables
Type: FEP jacket, plenum rated CMP/CL2P, UL/cUL listed, -67 to 302 ⁰F [-55 to 150 ⁰C], UV tolerant
Standard Lengths: 10, 25 and 50 ft. [3.1, 7.6 and 15.2 m]Connecting Plug: 0.60” [15.24 mm] nominal diameter
Power Requirement: 24 VAC (22.8 to 26.4 under load) @8V-A
User Interface: 16-character LCD display and 4 button interface
B.A.S. Connectivity Options
EF-A2000 Transmitter: Two field selectable (0-5/1-5/0-10/2-10 VDC), scalable and protected analog output signals (AO1=airflow or airflow 1, AO2=airflow 2, temperature or alarm)
* The VDC output circuit of the EF-A2000 transmitter can drive the input circuit of devices designed to measure 4-wire current loops with a resistive load ≥250 ohms.
EF-N2000 Transmitter: One field selectable (BACnet MS/TP or Modbus RTU) and non-isolated RS-485 network connection – Individual sensor node airflow rates and temperatures are available via the network (provide individual 24 VAC transformers for each EF-N2000 transmitter for applications requiring isolated RS-485)
Relay
Type: Dry Contact w/ onboard jumper to drive a remote LED (R1=alarm)
Status: N.O. or N.C. via user setup configuration
Rating: 30 VDC or 24 VAC @ 3 amp. max.
Airflow Alarm
Type: Low and/or high user defined setpoint alarm
Tolerance: User defined % of setpoint
Delay: User defined
Zero Disable: Alarm can be disabled when the airflow rate falls below the low limit cutoff value (unoccupied periods)
Reset Method: Manual or automatic
Visual Indication: Yes, LCD display
Network Indication: Yes (EF-N2000 only)
Analog Signal Indication: Yes, on AO2 assignment (EF-A2000 only)
Contact Closure Relay: Yes, on R1 assignment
System Status Alarm
Type: Sensor diagnostic system trouble indication
Visual Indication: Yes, LCD display
Network Indication: Yes (EF-N2000 only)
Analog Signal Indication: Yes, on AO2 assignment (EF-A2000 only)
Contact Closure Relay: Yes, on R1 assignment
¹Installed airflow accuracy is the actual system accuracy expected and includes sampling uncertainty of the sensor probes when installation meets or exceeds placement guidelines.