The CENSus-C100 is a unique solution for reliable and cost effective occupancy counting. Ideal for Demand Control Ventilation (DCV) applications. Designed for single width interior doors or openings. Multiple counters can be installed on rooms with more than one entry.
Counting Technology
Dual sensor differential thermal imaging
Accuracy
Typically better than ±5% of the actual population or 3 people, whichever is greater
Listings and Compliance
FCC: This device complies with Part 15 of the FCC rules
RoHS2: This device is RoHS2 compliant
Environmental Limits
Temperature (recommended limits): 65 to 85 ⁰F [18.3 to 29.4 ⁰C]Humidity: 5 to 95%
Sensors
Two thermopile sensors
Mounting Options
Standard: Install in overhead door jamb
Optional: Install above door opening with optional stand-off bracket
Maximum Recommended Mounting Height
96 in. [2.43 m]
Power Requirement
24 VAC (22.8 to 26.4 under load) @1.5V-A
B.A.S. Connectivity Options
CENSUS-C100: One 0-10 VDC, scalable and protected analog output signal (AO1=occupancy count) and one field selectable (BACnet MS/TP or Modbus RTU) and non-isolated RS-485 network connection (provide individual 24 VAC transformers for each CENSUS-C100 device for applications requiring isolated RS-485)
White powder-coated formed steel
© 2023, EBTRON, Inc.