EB-Flow

Series 2000
EF-x2000-T
Airflow Measurement with Temperature & Alarm Capability
EF-x2000-T
UL_Logo

EB-Flow

Series 2000
EF-x2000-T
Airflow Measurement with Temperature & Alarm Capability

The EF‐x2000‐T is EBTRON’s top‐of‐the‐line measurement solution for round ducts between 4 and 16 inches in diameter. Ideal for most small duct airflow measurement and volumetric airflow tracking applications. More features than the EF‐x1000‐T make this the best choice for all small duct measurement applications.

  • Thermal Dispersion Technology
  • Cost Effective Single Probe
  • Volumetric Airflow Calibration
  • %‐of‐reading Accuracy
  • Airflow and Status Alarm
  • Temperature Output Capability
  • Analog and RS‐485 Output Models
  • Dry Contact Relay
  • Remote Transmitter with LCD Display
  • 3‐year Warranty

Typical Applications

  • High-Performance CV/VAV Terminal Box Measurement
  • Small Duct Outdoor Air Delivery Monitoring
  • Small Duct Airflow Tracking
  • Hospital Pressurization
  • Laboratory Pressurization

Benefits

  • Improve Terminal Box Performance with Turndown
  • Comply with ASHRAE Standards
  • Satisfy LEED Prerequisites and Credits
  • Provide Acceptable IAQ
  • Save Energy
  • Reduce Liability
  • Improve Performance

Product Highlights

  • Accurate & Repeatable
  • Low Airflow Capability
  • Volumetric or Mass Airflow Measurement
  • Long-term Stability
  • “Plug-and-Play” Operation
  • Intuitive User Interface
  • Waterproof Sensor Assembly
  • FEP Plenum Rated Cable

GENERAL

Probe and Sensor Node Configurations

1 probe x 1 sensor node/probe (4 inch [101.6 mm] probe)
1 probe x 2 sensor nodes/probe (5 to 16 inch [127.0 to 406.4 mm] probes)

Installed Airflow Accuracy¹

Typically better than ±3% of reading

Sensor Node Averaging Method

Airflow: Independent arithmetic average
Temperature: Independent, velocity weighted or arithmetic average

Listings

UL: 60730-1; UL 60730-2-9 (HVAC Controls)

Environmental Limits

Temperature:
Probes: 0 to 2,000 fpm [0 to 10.16 m/s]: -20 to 160 ⁰F [-28.9 to 71.1 ⁰C]
Probes: 0 to 3,000 fpm [0 to 15.24 m/s]: 0 to 160 ⁰F [-17.8 to 71.1 ⁰C]
Transmitter: -20 to 120 ⁰F [-28.9 to 48.9 ⁰C]
Humidity: (non-condensing)
Probes: 0 to 100%
Transmitter: 5 to 95%

Individual Sensing Nodes

Sensing Node Sensors

Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe
Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Sensing Node Housing

Material: Glass-filled Polypropylene (Kynar® with /SS option)
Sensor Potting Materials: Waterproof marine epoxy

Sensing Node Internal Wiring

Type: Kynar® coated copper

Airflow Measurement

Accuracy: ±3% of reading to volumetric airflow standards (includes transmitter uncertainty)
Calibrated Range: 0 to 3,000 FPM [0 to 15.24 m/s]
Calibration Points: 7

Temperature Measurement

Accuracy: ±0.15 ⁰F [0.08 ⁰C] to NIST-traceable temperature standards (includes transmitter uncertainty)
Calibrated Range: -20 to 160 ⁰F [-28.9 to 71.1 ⁰C]
Calibration Points: 3

Sensor Probe Assembly

Tube

Material: Mill finish 6063 aluminum (316 stainless steel with /SS option)

Mounting Brackets

Material: 304 stainless steel

Mounting Options & Size Limits

Insertion: 4, 5, 6, 7, 8, 9, 10, 12, 14, and 16 inch round [101.6, 127.0, 152.4, 177.8, 203.2, 228.6, 254.0, 304.8, 355.6 & 406.4 mm]

Probe to Transmitter Cables

Type: FEP jacket, plenum rated CMP/CL2P, UL/cUL listed, -67 to 392 ⁰F [-55 to 200 ⁰C], UV tolerant
Standard Lengths: 3, 10, 25 and 50 ft. [0.9, 3.1, 7.6 and 15.2 m]
Connecting Plug: 0.60” [15.24 mm] nominal diameter

Transmitter

Power Requirement:

24 VAC (22.8 to 26.4 under load) @8V-A

User Interface:

16-character LCD display and 4 button interface

B.A.S. Connectivity Options

EF-A2000 Transmitter: Two field selectable (0-5/1-5/0-10/2-10 VDC*), scalable and protected analog output signals (AO1=airflow, AO2 = temperature or alarm)
* The VDC output circuit of the EF-A2000 transmitter can drive the input circuit of devices designed to measure 4-wire current loops with a resistive load ≥250 ohms.
EF-N2000 Transmitter: One field selectable (BACnet MS/TP or Modbus RTU) and non-isolated RS-485 network connection – Individual sensor node airflow rates and temperatures are available via the network (provide individual 24 VAC transformers at each EF-N2000 transmitter for applications requiring isolated RS-485)

Relay

Type: Dry Contact w/ onboard jumper to drive a remote LED (R1=alarm)
Status: N.O. or N.C. via user setup configuration
Rating: 30 VDC or 24 VAC @ 3 amp. max.

Airflow Alarm

Type: Low and/or high user defined setpoint alarm
Tolerance: User defined % of setpoint
Delay: User defined
Zero Disable: Alarm can be disabled when the airflow rate falls below the low limit cutoff value (unoccupied periods)
Reset Method: Manual or automatic
Visual Indication: Yes, LCD display
Network Indication: Yes (EF-N2000 only)
Analog Signal Indication: Yes, on AO2 assignment (EF-A2000 only)
Contact Closure Relay: Yes, on R1 assignment

System Status Alarm

Type: Sensor diagnostic system trouble indication
Visual Indication: Yes, LCD display
Network Indication: Yes (EF-N2000 only)
Analog Signal Indication: Yes, on AO2 assignment (EF-A2000 only)
Contact Closure Relay: Yes, on R1 assignment
¹Installed airflow accuracy is the actual system accuracy expected and includes sampling uncertainty of the sensor probes when installation meets or exceeds placement guidelines.